STAND-ALONE CONTROL UNIT WITHOUT SUPPLY TEMPERATURE SENSOR (SUPPLY TEMPERATURE MIGHT NOT BE HIGH ENOUGH) SHORT CIRCUIT – COMMON SUPPLY TEMPERATURE SENSOR
VITOCONTROL-S WITH VITOTRONIC 100 / VITOTRONIC 300-K WITH VITOTRONIC 200
VITOCONTROL-S CONTROLS IN A STAND-ALONE MANNER WITHOUT SUPPLY TEMPERATURE SENSOR (SUPPLY TEMPERATURE MIGHT NOT BE HIGH ENOUGH) COMMON SUPPLY TEMPERATURE SENSOR SHORTED OUT
VITOCROSSAL 300
REGULATES WITHOUT SUPPLY TEMPERATURE SENSOR (LOW-LOSS HEADER) SHORT CIRCUIT – SYSTEM FLOW TEMPERATURE SENSOR
VITODENS 200-W / 222-F
REGULATES WITHOUT SUPPLY TEMPERATURE SENSOR (LOW-LOSS HEADER) SHORT CIRCUIT – SUPPLY SYSTEM TEMPERATURE SENSOR
VITOTRONIC 020/200-H / 200 / 200-H / 300
MIXING VALVE CLOSES OR CLOSED SHORT CIRCUIT – SUPPLY TEMPERATURE SENSOR / MIXING VALVE CIRCUIT M1
VITORONIC 300-K WITH VITOTRONIC 100
VITOTRONIC 300-K, MW1S CONTROLS IN A STAND-ALONE MANNER WITHOUT STRAP-ON SENSOR (SUPPLY TEMPERATURE MIGHT NOT BE HIGH ENOUGH) SHORT CIRCUIT – STRAP-ON TEMPERATURE SENSOR
VITODENS 200-W
REGULATES WITHOUT SUPPLY TEMPERATURE SENSOR (LOW LOSS HEADER) SYSTEM SUPPLY TEMPERATURE SENSOR SHORTED OUT
Fault Code 55, 56 and 57
BOILER MODEL
SYSTEM BEHAVIOUR & DIAGNOSIS
VITOTRONIC 300-K WITH VITOTRONIC 200
CONTROL MODE MAINTENANCE OR FAULT ON VITOTRONIC 100 OF BOILER 5-8
Fault Code EE and EF
BOILER MODEL
SYSTEM BEHAVIOUR & DIAGNOSIS
VITODENS 100-W / 200 / 0 / VITOTRONIC 300
BURNER BLOCKED FAULTY AIR PRESSURE SWITCH – AIR DAMPER (FLAP) STUCK
Fault Code FE4
BOILER MODEL
SYSTEM BEHAVIOUR & DIAGNOSIS
VITOCROSSAL 200
BURNER SHUTS DOWN MULTIPLE DETECTION OF UNDERVOLTAGE
Fault Code F-B7, F-F4, F-F2, F-F7, F-F8 and F-F9
BOILER MODEL
SYSTEM BEHAVIOUR & DIAGNOSIS
VITOCROSSAL 200
CASE A: BURNER CONTROL UNIT IN A FAULT STATE; SYSTEM COOLS DOWN; BURNER CONTROL LOCKED OUT. CASE B: TYPE OF CODING CARD CASE A: CODING CARD NOT INSERTED IN THE BURNER CONTROL UNIT; FAULTY OR INCORRECT CODING CARD. CASE B: CODING CARD DOES NOT MATCH BURNER CONTROL UNIT
Fault Code 50, 51, 58 and 59
BOILER MODEL
SYSTEM BEHAVIOUR & DIAGNOSIS
VITODENS 200-W / 222-F
NO DHW HEATING / FAULT WITH DHW SHORT CIRCUIT/OPEN CIRCUIT – DHW TANK TEMPERATURE SENSOR OR LEAD BREAK
Fault Code A9, BA, BB, BC & FE0
BOILER MODEL
SYSTEM BEHAVIOUR & DIAGNOSIS
VITODENS 200
BOILER COOLS DOWN SENSOR INPUTS ARE NOT READ CORRECTLY
Fault Code F-FA, F-FB and FR
BOILER MODEL
SYSTEM BEHAVIOUR & DIAGNOSIS
VITOCROSSAL 200 / 400-620 / 186-311
FAN RUNS WITHOUT DEMAND; BURNER CONTROL UNIT IN A FAULT STATE FAN NOT STOPPED; CABLE 100A FAULTY; FAN FAULTY; BURNER CONTROL UNIT FAULTY
Fault Code 8C, 8D, 8E and 8F
BOILER MODEL
SYSTEM BEHAVIOUR & DIAGNOSIS
VITOTRONIC 300
BURNER CONTROL UNIT IN A FAULT STATE LEAD BREAK, BOILER WATER TEMPERATURE SENSOR, BURNER CONTROL UNIT
Fault Code 52
BOILER MODEL
SYSTEM BEHAVIOUR & DIAGNOSIS
VITOTRONIC 300
CONTROL MODE SHORT CIRCUIT – SUPPLY TEMPERATURE SENSOR LOW-LOSS HEADER
VITODENS 100-W COMBIPLUS
BURNER BLOCKED (COMBIPLUS ONLY) FLOW SENSOR SHORTED OUT
Fault Code 38
BOILER MODEL
SYSTEM BEHAVIOUR & DIAGNOSIS
VITODENS 200-W / 222-F / COMBIPLUS
BURNER BLOCKED BOILER WATER TEMPERATURE SENSOR CABLE BROKEN
BURNER IS SWITCHED ON AND OFF BY ADJUSTABLE HIGH LIMIT OPEN CIRCUIT – BOILER TEMPERATURE SENSOR
VITOTRONIC 300-K WITH VITOTRONIC 300
BURNER IS STARTED AND STOPPED VIA A TEMPERATURE CONTROLLER LEAD BREAK, BOILER WATER TEMPERATURE SENSOR
VITODENS 100-W
BURNER BLOCKED BOILER WATER TEMPERATURE SENSOR LEAD BROKEN
Fault Code A7
BOILER MODEL
SYSTEM BEHAVIOUR & DIAGNOSIS
VITOCONTROL-S WITH VITOTRONIC 100 /VITOTRONIC 100 / VITOTRONIC 300-K WITH VITOTRONIC 300
CONTROL MODE ISOLATION VALVE CONFIGURATION FAULT – OC:2, OC:3 OR OC:4 SET AND CODING 4E:1 NOT SET
Fault Code 0F
BOILER MODEL
SYSTEM BEHAVIOUR & DIAGNOSIS
VITODENS 222-F
CONTROL MODE CODE 0F IS ONLY DISPLAYED IN THE FAULT HISTORY (SERVICE REQUIRED)
VITOTRONIC 300 / VITOTRONIC 300-K WITH VITOTRONIC 300 / VITODENS 200-W / VITOCONTROL-S WITH VITOTRONIC 100
CONTROL MODE – CONTROLLED OPERATION CODE 0F IS ONLY DISPLAYED IN THE FAULT HISTORY (SERVICE REQUIRED)
VITOTRONIC 200 /300
NORMAL OPERATION SERVICE REQUIRED
VITOCONTROL-S, MW1 WITH VITOTRONIC 100 / VITOTRONIC 300-K, MW1S WITH VITOTRONIC 100
CONTROL MODE MAINTENANCE 0F IS ONLY DISPLAYED IN THE FAULT HISTORY
Fault Code E1, E7, E8, E9, EA, EB, EC and FF2
BOILER MODEL
SYSTEM BEHAVIOUR & DIAGNOSIS
VITODENS 200-W / 222-F /VITOTRONIC 300
BURNER IN FAULT MODE HEATING WATER FLOW RATE TOO LOW DURING CALIBRATION; FLOW SWITCH CAUSED SHUTDOWN
Fault Code 29, 41, 49, F80, F81, F83, F88 and F89
BOILER MODEL
SYSTEM BEHAVIOUR & DIAGNOSIS
VITOTRONIC 200 / 300
NORMAL OPERATION WITHOUT INFLUENCE OF RETURN WATER TEMPERATURE OPEN CIRCUIT 1 OR 2 – RETURN WATER TEMPERATURE SENSOR (OF MIXING VALVE CIRCUIT 1)
Viessmann Boiler Fault Code A3, B0, F1, E-E1 and F-E2
BOILER MODEL
SYSTEM BEHAVIOUR & DIAGNOSIS
VITOCROSSAL 300 / VITODENS 200-W / 222-F / 300
CONTROL MODE (STAYS IN FACTORY DEFAULT SETTING) FAULTY PROGRAMMING UNIT
Fault Code 28
BOILER MODEL
SYSTEM BEHAVIOUR & DIAGNOSIS
VITOCONTROL-S WITH VITOTRONIC 100
VITOCONTROL-S, VD2/CT3/CM2 CONTROLS IN A STAND-ALONE MANNER W/O SUPPLY TEMPERATURE SENSOR (SUPPLY TEMPERATURE MIGHT NOT BE HIGH ENOUGH) OPEN CIRCUIT – COMMON SUPPLY TEMPERATURE SENSOR
VITOCONTROL-S WITH VITOTRONIC 100 / VITOTRONIC 300-K WITH VITOTRONIC 100
VITOCONTROL-S, WB2B CONTROLS IN A STAND-ALONE MANNER W/O SUPPLY TEMPERATURE SENSOR (SUPPLY TEMPERATURE MIGHT NOT BE HIGH ENOUGH) COMMON SUPPLY TEMPERATURE SENSOR CABLE BROKEN
VITOCROSSAL 300 / VITODENS 200-W / 22-F
REGULATES WITHOUT SUPPLY TEMPERATURE SENSOR (LOW-LOSS HEADER) SYSTEM SUPPLY TEMPERATURE SENSOR CABLE BROKEN
VITOTRONIC 050/200-H
MIXING VALVE CLOSES CABLE BREAK – SUPPLY TEMPERATURE SENSOR
VITOTRONIC 050/200-H
MIXING VALVE IS CLOSED OPEN CIRCUIT – SUPPLY TEMPERATURE SENSOR OF MIXING VALVE CIRCUIT M1
VITOTRONIC 200-H / VITOTRONIC 200 / 300
MIXING VALVE IS BEING CLOSED LEAD BREAK, SUPPLY TEMPERATURE SENSOR, HEATING CIRCUIT WITH MIXING VALVE M1 (HEATING CIRCUIT 1)
VITOTRONIC 300 / 300-K WITH VITOTRONIC 300 / 200
STAND-ALONE CONTROL UNIT WITHOUT SUPPLY TEMPERATURE SENSOR (SUPPLY TEMPERATURE MIGHT NOT BE HIGH ENOUGH) LEAD BREAK, COMMON SUPPLY TEMPERATURE SENSOR
VITOTRONIC 300-K WITH VITOTRONIC 100
VITOTRONIC 300-K, MW1S CONTROLS IN A STAND-ALONE MANNER W/O STRAP-ON SENSOR (SUPPLY TEMPERATURE MIGHT NOT BE HIGH ENOUGH) OPEN CIRCUIT – STRAP-ON TEMPERATURE SENSOR
Fault Code B1
BOILER MODEL
SYSTEM BEHAVIOUR & DIAGNOSIS
VITOCONTROL-S WITH VITOTRONIC 100 / VITOTRONIC 100 / 200 / 300 / VITOTRONIC 300-K WITH VITOTRONIC 100
EMISSIONS TEST MODE INTERNAL ELECTRONICS FAULT
VITOCONTROL-S WITH VITOTRONIC 100 / VITODENS 200-W
REGULATES AS IF THE OUTSIDE TEMPERATURE IS 32°F (0°C) INTERNAL FAULT
VITOTRONIC 020/200-H
UNDEFINED CONTROL CHARACTERISTICS INTERNAL ELECTRONICS FAULT
CONTROL MODE – LEAD BREAK, LOW-LOSS HEADER SUPPLY TEMPERATURE SENSOR BURNER BLOCKED / CONTROL MODE – SENSOR CABLE BROKEN
CC and F0
BURNER IN FAULT MODE IONISATION CURRENT TOO HIGH DURING CALIBRATION – BOILER TEMPERATURE LIMITER RESPONDED (F2) – AIR OR BLOCKAGE IN SYSTEM/PUMP FAILURE
B6
CONTROL MODE OPEN CIRCUIT – KM BUS TO SOLAR CONTROL UNIT – EXTENSION AM1 / DE1-DE3 M1 – COMMUNICATION FAULT
D5
BURNER BLOCKED FLUE GAS TEMPERATURE SENSOR NOT PROPERLY POSITIONED / CHECK SENSOR EXTERNAL PUMP FITTED ON THE SYSTEM (100-W) A-3 FAULT
60, 68, 70, 78, BD, BE and BF
NO OUTPUT REDUCTION – RETURN CONTROL OPEN – BOILER WITH MAXIMUM TEMPERATURE SHORT/OPEN CIRCUIT – TEMPERATURE SENSOR [17A]
E2 and E3
BURNER BLOCKED – FAULT: SUPPLY VOLTAGE 24V
40 and 44
MIXING VALVE CLOSES HEATING CIRCUIT 2 WITH MIXING VALVE SUPPLY SHORT CIRCUIT ON TEMPERATURE SENSOR
48 and 4C
MIXING VALVE CLOSES OR CLOSED HEATING CIRCUIT 2 WITH MIXING VALVE SUPPLY TEMPERATURE SENSOR CABLE BROKEN / OPEN CIRCUIT
FC
BURNER IN FAULT MODE GAS VALVE FAULTY OR FAULTY MODULATION VALVE CONTROL / OR VENT SYSTEM BLOCKED. CHECK THE FAN, FAN CABLE AND PCB
FE
BURNER BLOCKED OR IN FAULT MODE STRONG INTERFERENCE (EMC) FIELD NEARBY OR FAULTY MAIN PCB
B2
CONTROL MODE – INTERNAL ELECTRONICS FAULT
B5
CONTROL MODE – EXTERNAL SAFETY EQUIPMENT
80, 81, 82, 83 and FD
BURNER CONTROL UNIT IN A FAULT STATE; SYSTEM COOLS DOWN; BURNER CONTROL UNIT LOCKED OUT SHORT CIRCUIT – BOILER WATER TEMPERATURE SENSOR, BURNER CONTROL UNIT
B4
NORMAL OPERATION / FAULT AROUND BURNER CONTROL UNIT INTERNAL FAULT (PCB)
C2-C8, CD-CF, D2-D8, DA-DF and E0
BOILER COOLS DOWN FIXED HIGH LIMIT HAS RESPONDED OR FUSE F2 HAS BLOWN
F5
GAS PRESSURE SWITCH SHOWS NO GAS PRESSURE / ELECTRICAL CONNECTION FAULT GAS SHUT-OFF VALVE CLOSED; GAS PRESSURE SWITCH FAULTY; MULTIPLE GAS PROBLEMS WITH GAS SUPPLY
F6, 58, F9, F-E1, F-E2 and F-F6
BURNER IN FAULT MODE / EMERGENCY OPERATION FAN NOT AT STANDSTILL / PLUG-IN CONNECTION